Before using the Strella app, program your ripening rooms to the following settings. These settings will become the system default across rooms and remain active across ripening cycles.

Contact your Account Manager if you have any questions or would like to discuss specific facility and room manufacturer settings.

Holding Temperature: 58

Regular venting: 30 min every 3 hours

Post-gas venting: 60 min

Auto gas set point (default reference temp): 60°F

Auto-gas duration: 24 hours

Humidity set point: 90%

Zone mode: HOLD

Controlling sensor for zone temp: PULP (not DA (discharge) or RA (return))

Controlling sensor for gas initiation: PULP

Auto gas gas on temp source: AV

Ethylene generator: