When using Strella app, program your ripening rooms using these settings.

Holding Temperature: 58

Regular venting: 30 min every 3 hours

Post-gas venting: 60 min

Auto gas set point (default reference temp): 60°F

Auto-gas duration: 24 hours

Humidity set point: 90%

Zone mode: HOLD

Controlling sensor for zone temp: PULP (not DA (discharge) or RA (return))

Controlling sensor for gas initiation: PULP

Auto gas gas on temp source: AV

Ethylene generator:

Contact your Account Manager for questions and to discuss facility-specific scenarios.